Model and meaning
Main technical parameters
technical parameter |
specifications | DNH1-250 | DNH1-160 | |||||
Rated working voltage | Ue | V | AC400 | AC690 | AC400 | AC690 | ||
Rated working current | Ie | A | 250 | 200 | 160 | 100 | ||
Agreed heating current | Ith | A | 250 | 200 | 160 | 100 | ||
Rated limited short-circuit current (with fused core) | KA | 100 | 50 | 100 | 50 | |||
Usage category (with fused core) | AC-23B | AC-23B | AC-23B | AC-23B | ||||
Rated insulation voltage | Ui | V | AC1000 | AC1000 | AC1000 | AC1000 | ||
Rated impulse withstand voltage | Uimp | KV | 12 | 12 | 12 | 12 | ||
Rated frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | |||
Electrical life (number of cycles) | times | 200 | 200 | 200 | 200 | |||
Maximum torque | N.m | 30 | 30 | 20 | 20 | |||
Fusible core |
Executive standards:IEC60269-2/GB/T 13539.2 | 1 | 1 | 00 | 00 | |||
Rated working current | In | A | 200 | 200 | 160 | 100 | ||
power dissipation | Pn | W | 23 | 32 | 12 | 12 | ||
Normal use, installation, and transportation conditions | Ambient air temperature | -5℃~+40℃ | ||||||
Altitude | ≤2000m | |||||||
Installation category and pollution level | Ⅲ、Ⅳ | 3 | ||||||
Transportation and Storage | -25℃~+55℃ |
Product Installation Method (160A)
Product Installation Method (250A)
Click to view grl group company information>>
Click to view grl Fuse Switch Disconnector product>>
Click to view grl fuse product>>